CVE Explorer
CVE-2025-9042
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
Known exploited
Not asserted
Disputed
No
Stale source
No
Conflicts
0
Affected products and versions
1 source assertion{"defaultStatus":"unaffected","product":"FLEX 5000 I/O","vendor":"Rockwell Automation","versions":[{"status":"affected","version":"Version 2.011 or below"}]}
- cve_program_cvelist_v5affectedurn:baitaphish:normalized-source-record:v2:cf26761caec7a02e237d08ae6d275b84321adcff427bbc4dbfd5fa8ccc80c5d0 · sha256:b1c609c1945cbc26… · /containers/cna/affected/0
Provider-owned CVSS observations
1 source assertion{"metric":{"Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","Safety":"NOT_DEFINED","attackComplexity":"LOW","attackRequirements":"NONE","attackVector":"NETWORK","baseScore":8.7,"baseSeverity":"HIGH","privilegesRequired":"NONE","providerUrgency":"NOT_DEFINED","subAvailabilityImpact":"NONE","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","userInteraction":"NONE","valueDensity":"NOT_DEFINED","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","version":"4.0","vulnAvailabilityImpact":"HIGH","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"NON…
- cve_program_cvelist_v5cvssurn:baitaphish:normalized-source-record:v2:cf26761caec7a02e237d08ae6d275b84321adcff427bbc4dbfd5fa8ccc80c5d0 · sha256:b1c609c1945cbc26… · /containers/cna/metrics/0/cvssV4_0
CWE assertions
1 source assertion{"cweId":"CWE-1287","description":"CWE-1287: Improper Validation of Specified Type of Input","lang":"en","type":"CWE"}
- cve_program_cvelist_v5cweurn:baitaphish:normalized-source-record:v2:cf26761caec7a02e237d08ae6d275b84321adcff427bbc4dbfd5fa8ccc80c5d0 · sha256:b1c609c1945cbc26… · /containers/cna/problemTypes/0/descriptions/0
Source references
1 source assertion{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html"}
- cve_program_cvelist_v5referenceurn:baitaphish:normalized-source-record:v2:cf26761caec7a02e237d08ae6d275b84321adcff427bbc4dbfd5fa8ccc80c5d0 · sha256:b1c609c1945cbc26… · /containers/cna/references/0
Attribution and limitations
- CVE Program CVEList V5: Reproduce the MITRE copyright designation and CVE license in copies. Source →
Provider severity values are preserved separately. Baitaphish does not convert them into a risk rating, infer affected products, or treat EPSS as observed exploitation.